Scope: Combination Wave Test System is one of a special test machines, it can output 1.2/50μs open circuit voltage wave and 8/20μs short current wave. The test system can be used for carrying VPR Test, Surge Immunity Test and so on. The test system contends the requirements of IEC 61643, IEC 61000-4-5 and UL 1449 standards.
10/250 Combination wave 1.2/50 & 8/20 Combination wave 10/360 Combination wave
Main specifications are as follows
Combination Wave | Short Circuit Current | Open Circuit Voltage | Virtual Impedance | ||||
Front Time | Duration Time | Peak | Front Time | Duration Time | Peak | ||
6kV/600A | 10μs | 250μs | 600A 0%,16% | 10μs (-6μs,+0) | 250μs (-0,+150μs) | 6kV 0%,16% | 10 ± 1.6Ω |
6kV/150A | 10μs | 250μs (-0,+108μs) | 150A 0%,15% | 10μs (-2.5μs,+0) | 250μs (-0,+108μs) | 6kV 0%,15% | 40 ± 6Ω |
6kV/150A | 5μs | 320μs | 150A | 5μs | 320μs | 6kV | 40 |
6kV/1.2kA | 2μs | 10μs | 1.2kA 0%,+20% | 2μs (-1,+0) | 10μs (-0,+7) | 6kV 0%,+20% | 5 ± 1Q |
6kV/3kA | 8μs ± 1.6μs | 20μs ± 4μs | 3kA ± 10% | 1.2μs ± 3.6μs | 50μs ± 10μs | 6kV ± 10% | 2 ±0.5Ω |
Operating duty test | AC Source: 0-1000V /5-100A. Phase tracking and control accuracy: 0-360° ±5° DC Source:0-1500V /5-100A | ||||||
Standard | IEC61643,IEC61000-4-5,UL1449,IEC60060 |
ADDRESS: No.1,Huoju Road, Beilin District, Xi'an,Shaanxi, China
TEL:86-(0)-82681326 86-(0)-83204290
E-mail: jddyjs@163.com