Scope: ICTS 8/20&10/350 Impulse Current Test System is a special test machines, it can output 8/20μs, 10/350μs current wave. The test system is used for carrying VPR Test, Residual Voltage Test, ClassⅠ and Class Ⅱ Classification Test, Operating Duty Test and so on. The test system contends the requirements of IEC 61643 and UL 1449 standards.
300kA(8/20) and 70kA(10/350) impulse current test system
200kA(8/20) and 50kA(10/350) impulse current test system
200kA(8/20) and 50kA(10/350) impulse current test system
Main specifications are as follows
Operating duty test
Impulse
current | 8/20 Impulse Current | 10/350 Impulse Current | Impedance | ||||
Front Time | Duration
Time | Peak | Front Time | Duration
Time | Peak | ||
200/50 | 8μs | 20μs ± 10% | 200kA | 10μs (-10,100)% | 350μs ± 20% | 50kA | 2Ω... |
200/30 | 200kA | 30kA | 2Ω... | ||||
150/30 | 150kA | 30kA | 2Ω... | ||||
150/20 | 150kA | 20kA | 2Ω... | ||||
150/20 | 120kA | 20kA | 2Ω... | ||||
Operating duty test | AC Source: 0-1000V /5-100A. Phase tracking and control accuracy: 0-360° ±5° DC Source:0-1500V /5-100A | ||||||
Standard | IEC61643,UL1449,IEC60060 |
ADDRESS: No.1,Huoju Road, Beilin District, Xi'an,Shaanxi, China
TEL:86-(0)-82681326 86-(0)-83204290
E-mail: jddyjs@163.com